LQR CONTROL APPROACH APPLIED TO UNINTERRUPTIBLE POWER SUPPLY (UPS)
This paper presents a control strategy applied to high power uninterruptible power supplies with a low switching frequency. In the controller design, the gains are determined by minimizing a cost function, which reduces the tracking error and smoothes the control signal. A recursive least square estimator identifies the parameters model at different load conditions. Then the linear quadratic controller gains are adapted periodically. The output voltage is the only state variable measured.The other state
variables are obtained by estimation process. Simulation results show that the proposed control strategy offers good
performances for either linear and non-linear loads with low total harmonic distortions (THD) even at low frequencies making it very useful for high power applications.
Auteur(s)
Boualaga Rabhi
Moussi A.
Articles de cet auteur
- Reflection optimization of a multicrystalline solar cell embedded in a photovoltaic module
- Rende Ment Maximise D’un Moteur Asynchrone Alimente Par Une Source Photovoltaïque
- Photovoltaic Pumping Systems Technologies Trends
- Etude Comparative Entre Les Techniques D’optimisation des systemes de pompage
- An Improved Efficiency Permanent Magnet Brushless Dc Motor PV Pumping System
- [...]
Mots-clés
- Adaptive control
- Linear quadratic regulator
- Parameter estimation
-
Simulation
-
- Solar Charger Sizing
- Effect of a buffer layer on the Performance of Thin-film Cu(In,Ga)Se2 Solar Cells
- Numerical simulation of radiation damage on the device performance of GaAs MESFETs
- Electrical characteristics of Organic Light Emitting Diode “OLED” finite difference modeling
- Design and simulation of a valveless piezoelectric micropump for fuel delivery in fuel cell devices
- Uninterruptible power supplies